Key Product Features

Complete Enclosure
UTEC’s package substation transformer comes fully enclosed within a compact unit, including the transformer itself, High Voltage (HV) and Low Voltage (LV) connections, and switchgear. This pre-assembled design ensures efficient installation and reduces on-site assembly time.
Versatile Application
Ideal for areas requiring underground power distribution, such as residential, commercial, and industrial developments, our transformer delivers seamless and reliable energy supply where it’s needed most.
Hermetically Sealed Design
The oil-immersed, hermetically sealed design guarantees optimal performance and safety. This feature ensures that the transformer operates efficiently while minimizing the risk of oil leakage or contamination.
Efficient Cooling System
The transformer’s flexible corrugated tank walls or radiators are crucial in maintaining optimal operating temperatures. This innovative cooling system ensures consistent performance even during demanding conditions.
Flexible Bushing Configuration
HV and LV bushings are strategically positioned for easy accessibility and maintenance. The HV bushings are plug-in type, while the LV bushings are designed as flat bars. Customization options, including porcelain-type bushings, are also available to cater to specific project requirements.

Proven Performance

Reliability

Count on consistent and uninterrupted power distribution, ensuring your operations run smoothly without disruptions.

Efficiency

Experience efficient energy conversion and distribution, leading to optimized energy usage and reduced losses.

Durability

Our transformers are designed for longevity with minimal maintenance requirements.

Safety

Our hermetically sealed design and stringent quality control measures prioritize safety for equipment and personnel, meeting and exceeding industry standards.

Technical Data

General Specification
Installation Type
Compact Substation
Standard Compliance
IEC60076 / 51-SDMS-02
Power Rating
Up to 1500 KVA
Polarity
3 phases
HV System Voltage
Up to 36 KV
LV System Voltage
Up to 1000 V
Rated Frequency
50/60 Hz
Insulation Method / Class
Mineral or Silicon Oil / Class A
Vector Group
DYN11
Cooling Type
ONAN/KNAN
Ambient Temperature
55 C
Max Temperature Rise for Oil
45 C
Max Temperature Rise for Winding
50 C
Tap Circuit Type / No of Positions
Off Circuit / 5 position ± 2×2.5 %