Key Product Features

Predictive Maintenance with LV Thermal Monitoring
BlokSeT sets the industry standard with LV system thermal monitoring. Permanently installed sensors accurately monitor busbar connections, cable compartments, and breaker contacts. Predictive maintenance capabilities mean you can address potential issues
Zero Downtime Tolerance
BlokSeT LV switchboards are built to endure harsh environments. They offer zero downtime tolerance and rapid restarting capabilities, ensuring your operations continue without interruption.
Certified to International Standards
Our switchboards are certified per IEC 61439-1&2 and international LV standards, guaranteeing top-tier quality and performance.
Recognized LV Panel for Internal Arc Safety
BlokSeT is recognized for its exceptional internal arc performance, providing a secure environment even in extreme conditions.
Green Premium Product
BlokSeT is a Green Premium product, demonstrating our commitment to environmental sustainability.
Localized Support
Troubleshooting and maintenance are made easier with our localized support, ensuring you receive assistance when and where you need it.

Proven Performance

BlokSeT Thermal Monitoring

This sets the benchmark for operational safety in LV power applications. BlokSet delivers proven performance by: 1. Early Detection. Permanently installed sensors continuously monitor your LV switchboards, offering early detection of potential hazards. I

Operational Safety

BlokSeT LV switchboards are tailored to address the demand for superior operational safety in high-performance LV power applications.

Long-Term Trending Data

Our Thermal Monitoring provides long-term trending data, helping facility managers detect gradual deterioration and proactively address issues.

Optimized Maintenance

With predictive, condition-based maintenance, you can optimize maintenance schedules, ensuring the right work is done at the right time and place, ultimately saving time and resources.

Technical Data

Genaral data
Standards
IEC 61439-1/-2, IEC 61921, IEC TR 61641, IEC 60529, IEC 60068-2-11, IEC 60721-3-3 & IEC 61000-x-x
Certificate
Certified by recognized certification bodies ASEFA, ASTA, Dekra, and tested by independent laboratories
Electrical data
Rated insulation voltae Ui
1000 V 3~
Rated operating voltage Ue
690 V 3~
Rated impulse withstand voltage Uimp
Up to 12 kV
Overvoltage category
Up to IV
Degree of pollution
3
Rated frequency
50/60 Hz
Main Busbar: Rated current Ie
Up to 7000 A
Main Busbar: Rated peak withstand current Ipk
Up to 220 kA
Main Busbar: Rated short-time withstand current Icw
Up to 100 kA rms - 1 s [1]
Distribution busbar: Rated current Ie
Up to 3200 A
Distribution busbar: Rated peak withstand current Ipk
Up to 220 kA
Distribution busbar: Rated short-time withstand current Icw
Up to 100 kA rms - 1 s [2]
Arc fault containment: Prospective short-circuit current
Up to 100 kA
Arc fault containment: Duration
0.4 s
Arc fault containment: Criteria (IEC TR 61641)
1 to 7
Earthing system
TT-IT-TNS-TNC
Mechanical data
Form of separation
Up to Form 4b
Withdrawability
FFF/WWW
Seismic
UBC 97, IBC 2006 / AC 156 (site class B-C-D, floor level only) / IEC 68-3-3 (equivalent to Richter scale up to level 9) / IEEE 693 / GOST 17516.1-90 (civil market, all seismic intensity, up to installation level 2) / 2G, zone 4
Installation
Indoor - environment type 2, EMC – Type A as per IEC 61439
Degree of protection
Up to IP54
Operating temperature
-5°C to 50°C
Vibration
IACS E10 / 0.7G
Corrosive atmosphere
H2S and SO2 (IEC 60721-3-3) / Up to 3C2
[1] For Main Busbar Icw = 150 kA rms - 1S and 86 kA rms - 3 s contact Schneider Electric
[2] For VBB Icw = 65 kA rms - 3 s contact Schneider Electric

Low-Voltage Main Distribution Boards: Power Under Control